Peerless Fire Pump
Compliance with NFPA-20 and UL Listed FM Approved.
Horizontal Split Case Fire Pump
Peerless Fire Pump offers a range of split case pumps with spacing-saving designs to simplify pump room layout. The AEF Models fire pump is designed to provide water to stand pipe, sprinkler, chemical mitigation and hydrant systems for fire suppression in industrial facilities. Suction and discharge flanges are on a common centerline for easy installation.
Code Compliance: NFPA-20, UL, ULC, FM, ANSI/H.I.
-
Capacities: 250 ~ 5,000 gpm (57 ~1,136 m3/hr)
-
Head: 92 ~ 664 feet (28-202 m)
-
Pressure: 40 ~288 psi (2.75-19.8 bar)
-
Horsepower: Up to 1,000 hp (745 kW)
-
Temperature: Ambient within the limits for satisfactory equipment operation
-
Drives: Electric motors, diesel engines
-
Liquids: Potable/non-potable water, salt water
-
Materials: Cast iron, bronze fitted as standard.
-
Optional materials available for sea water applications.
Vertical Turbine Fire Pump
Peerless Pump offers vertical turbine fire pumps with space-saving designs. The turbines are designed for stand pipe, sprinkler, chemical mitigation and hydrant systems. The modular construction assures complete flexibility in selecting a pump. Bowls and suction bell are bolted together allowing for easier disassembly. Dynamically balanced impellers are secured to the shaft with steel locking.
Code Compliance: NFPA-20, UL, ULC, FM, ANSI/H.I.
-
Capacities: 250-5,000 gpm (57 ~1,136 m3/hr)
-
Head: 40 ~ 183 psi
-
Pressure: Dependent on material
-
Horsepower: Compliant with NFPA, UL, FM
-
Temperature: Above 40°F (5°C)
-
Drives: Electric motors, right angle gear drives, steam turbines, combination drives
-
Liquids: Fresh and sea water, others as needed
-
Materials: Cast Iron, Bronze Fitted is standard. Option is available for Duplex, stainless steel, aluminum, bronze, nickel aluminum bronze, K Monel
In-Line Fire Pump
Peerless Pump offers a range of vertical in-line pumps. The PVF pumps are designed to provide water to stand pipe, sprinkler, chemical mitigation and hydrant systems for fire suppression in industrial facilities. The vertical design requires 25~30% less space than a traditional horizontal split case pump design. In-line equal sized suction and discharge flanges make this a great option for retrofits. The top pullout construction allows for servicing the pump without disturbing connecting piping.
Code Compliance: NFPA-20, UL, ULC, FM, ANSI/H.I.
-
Capacities: 50 ~ 1,500 gpm (11 ~ 340 m3/hr)
-
Head: Up to 406 feet (123 m)
-
Pressure: Up to 175 psi (12 bar)
-
Horsepower: Up to 125 hp (93 kW)
-
Temperature: Ambient within the limits for satisfactory equipment operation
-
Drives: Electric motors
-
Liquids: Potable/non-potable water, salt water
-
Materials: Cast iron, bronze fitted